Weidmuller 8705640000

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Weidmuller 8705640000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CULUS, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-20
- eClass 9.0
- 27-21-01-20
- eClass 9.1
- 27-21-01-20
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- UNSPSC
- 30-21-18-01
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Type of connection
- Screw connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 96.5 mm
- Length (inches)
- 3.799 inch
- Net weight
- 132 g
- Width
- 17.5 mm
- Width (inches)
- 0.689 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Configuration
- DIP switch and potentiometer, Alarm status reset via reset input or button
- Galvanic isolation
- 3-way isolator
- Rail
- TS 35
- Repeat accuracy
- < 0.3 % of set range
- Step response time
- < 300 ms
- Temperature coefficient
- ≤ 250 ppm/K of measuring range
- Voltage supply
- from the measuring circuit
Input
- Input frequency
- 50...60Hz
- Input voltage
- 24...70 / 70...140 / 140...210 / 210...260 V AC / DC, max. 260 V AC ⁄ DC
- Number of inputs
- 1 x single-phase (L, N)
Insulation Coordination
- Clearance & creepage distances
- ≥ 3 mm
- EMC standards
- EN 61000-6-2, EN 61000-6-4
- Galvanic isolation
- 3-way isolator
- Impulse withstand voltage
- Input/output, input/reset input, reset input/output: 4 kV
- Insulation voltage
- 2 kVeff
- Pollution severity
- 2
- Rated voltage
- input/output, input/reset input, reset input/output: 300 V
- Surge voltage category
- III
Output (Digital)
- Alarm function
- configurable, Surge voltage, Undervoltage, Hysteresis: 10 V
- Continuous current
- 3 A
- Max. switching voltage, AC
- 250 V
- Type
- Relay, 1 CO contact
Probability Of Failure
- MTTF
- 587 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- -10 °C...55 °C
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- -10 °C
- Storage temperature
- -20 °C...70 °C
- Storage temperature, max.
- 70 °C
- Storage temperature, min.
- -20 °C
Tender Specification Sheets
- Long specification
- Limit-value monitoring component for 1-phase AC / DC voltages with relay outputand electrical isolationlimit-value monitoring component in 17.5 mm width for recording AC / DCvoltages 24...70 V / 70...140 V / 140...210 V / 210...260 V.A relay contact (CO) with a switching capacity of 750 VAis available on the output side.Input ranges, high/low tripswitching behaviour, hysteresis and memory behaviour can be configured using DIP switches. Switching threshold can be adjusted with front-side potentiometerPower is supplied using the measured circuit.The memory function can be activated using an external reset input 18...30 VDC.Input/output/reset have 4 kV of electrical isolation.Add-on housing for TS35 rail mountingDimensions: L/W/H 96.5/ 17.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 24...70 V / 70...140 V / 140...210 V / 210...260 V AC/DC. SwitchableVoltage of measuring circuit max 260 VOutput Relay / COSwitching current 3 ASwitching voltage 6... 250 V AC / 6...60 V DCSwitching threshold 10...90 % via potentiometerHysteresis 24...70 V switchable 5 V / 10V 70...260 V switchable 8 V / 16 V Temperature coefficient < 250 ppm KStep response time < 300 msReset input 18...30 VDC / max 700 msAmbient temperature range 0 °C...+50 °C Secure isolation EN 50178, 2-way isolation up to 4 kVTest voltage 2 kVeff Input / Output / Reset inputRated voltage 300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULusType WA5 VMR 1ph
- Short specification
- Limit-value monitoring component for 1-phase AC / DC voltages with relay output and electrical isolationlimit-value monitoring component in 17.5 mm width for recording AC / DC voltages 24...70 V / 70...140 V / 140...210 V / 210...260 V. A relay contact (CO) with a switching capacity of 750 VA is available on the output side. Input ranges, high/low trip switching behaviour, hysteresis and memory behaviour can be configured using DIP switches. Switching threshold can be adjusted using the front-side potentiometer. The input circuit is used for the power supply. The memory function can be activated using an external reset input 18...30 VDC. The input/output/reset have 4 kV of electrical isolation.
Reviews
What our customers say
Rating