Weidmuller 8705630000

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Weidmuller 8705630000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CULUS, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-20
- eClass 9.0
- 27-21-01-20
- eClass 9.1
- 27-21-01-20
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- UNSPSC
- 30-21-18-01
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Type of connection
- Screw connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 96.5 mm
- Length (inches)
- 3.799 inch
- Net weight
- 120.6 g
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Configuration
- DIP switch and potentiometer, Alarm status reset via reset input or button
- Galvanic isolation
- 3-way isolator
- Rail
- TS 35
- Repeat accuracy
- < 0.3 % of set range
- Step response time
- < 300 ms
- Temperature coefficient
- ≤ 300 ppm/K
- Voltage supply
- from the measuring circuit
Input
- Input frequency
- 50...60Hz
- Input voltage
- 80…250 V AC/DC 3~, 200...400 V AC/DC
- Number of inputs
- 1 x three-phase (R, S, T, N)
Insulation Coordination
- Clearance & creepage distances
- Output circuit: 1.8 mm; input circuit, output circuit 1/output circuit 2: 3 mm; input/output: 5.5 mm
- EMC standards
- EN 61000-6-1, 2, 3, 4
- Galvanic isolation
- 3-way isolator
- Impulse withstand voltage
- 6 kV
- Insulation voltage
- 4 kVeff / 1 min.
- Pollution severity
- 2
- Rated voltage
- 600 V
- Surge voltage category
- III
Output (Digital)
- Alarm function
- configurable, Surge voltage, Undervoltage, Hysteresis: 10 V
- Continuous current
- 3 A
- Max. switching voltage, AC
- 250 V
- Type
- 2 CO contacts
Probability Of Failure
- MTTF
- 493 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- 0 °C...50 °C
- Operating temperature, max.
- 50 °C
- Operating temperature, min.
- 0 °C
- Storage temperature
- -25 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -25 °C
Tender Specification Sheets
- Long specification
- Limit-value monitoring component for 1- /3- phase AC and DC voltageswith relay output and electrical isolationlimit-value monitoring component in 22.5 mm width for recording 1-phaseAC/DC voltages 200...400 V or 3-phase AC- voltages of 80...250 V.A relay contact (CO) with a switching capacity of 750 VAis available on the output side.Input ranges, high/low trip alarm, monitored voltage window andswitching behaviour (for working and quiescent currents) can be configured using DIP switchesSwitching threshold can be adjusted with front-side potentiometerPower is supplied via the measured circuit. The I/O circuits have 6 kV of electrical isolation.Add-on housing for TS35 rail mountingDimensions: L/W/H 96.5/ 17.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 3 phases 80 V...250 V AC 1 phase 200...400 V AC/DC switchableVoltage of measuring circuit max 400 VOutput Relay / COSwitching current 3 ASwitching voltage 6... 250 V AC / 6...60 V DCSwitching threshold via potentiometerVoltage window small 10 % AC / 20 % DC // large 12 % AC / 25 % DC adjustableHysteresis 5 % AC / 6 % DC of inputTemperature coefficient < 300 ppm KStep response time < 300 msAmbient temperature range 0 °C...+50 °C Secure isolation EN 50178, 2-way isolation up to 6 kVTest voltage 4 kVeff / 1 min. Input / OutputRated voltage 600 V AC/DC at overvoltage category III and pollution degree 2Approvals cULusType WA5 VMR 3ph
- Short specification
- Limit-value monitoring component for 1- /3- phase AC and DC voltageswith relay output and electrical isolationlimit-value monitoring component in 22.5 mm width for recording 1-phaseAC/DC voltages 200...400 V or 3-phase AC- voltages of 80...250 V.A relay contact (CO) with a switching capacity of 750 VAis available on the output side.Input ranges, high/low trip alarm, monitored voltage window andswitching behaviour (for working and quiescent currents) can be configured using DIP switchesSwitching threshold can be adjusted with front-side potentiometerPower is supplied via the measured circuit. The I/O circuits have 6 kV of electrical isolation.