Weidmuller 8638950000

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Weidmuller 8638950000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CULUS, CULUSEX, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-29
- eClass 9.0
- 27-21-01-29
- eClass 9.1
- 27-21-01-29
- ETIM 6.0
- EC002919
- ETIM 7.0
- EC002919
- UNSPSC
- 30-21-18-01
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Stripping length, rated connection
- 7 mm
- Tightening torque, max.
- 0.5 Nm
- Tightening torque, min.
- 0.4 Nm
- Type of connection
- Screw connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 92.4 mm
- Length (inches)
- 3.638 inch
- Net weight
- 103.5 g
- Weight
- 100 g
- Width
- 17.5 mm
- Width (inches)
- 0.689 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Accuracy
- Slow/fast step response time: 0.5% of measuring range or 0.5 K/ 1% of measuring range or 1 K
- Configuration
- DIP switch
- Current-carrying capacity of cross-connect.
- ≤ 2 A
- Galvanic isolation
- 3-way isolator
- Input/Output
- configurable
- Linearity
- Yes
- Power consumption
- 880...980...1030 mW at IOUT = 20 mA
- Rail
- TS 35
- Step response time
- Fast: 1.2 s/ slow: 2.2 s
- Temperature coefficient
- span ≥ 100 K: ≤ 250 ppm/K of measuring range40 K <= span <= 100 K: <= 400 ppm/K of measuring range
- Voltage supply
- 24 V DC ± 20 %
Input
- Line resistance in measuring circuit
- 5 Ω Cu 10; 15 Ω Cu 25; 25 Ω Cu 50; 50 Ω Cu 100
- Number of inputs
- 1
- Sensor
- 3-/4-wired, Cu 10. Cu 25, Cu 50. Cu 100
- Temperature input range
- Adjustable from -200...+260°C
Insulation Coordination
- Clearance & creepage distances
- ≥ 3 mm
- EMC standards
- EN 55011, EN 61000-6
- Galvanic isolation
- 3-way isolator
- Impulse withstand voltage
- 4 kV
- Insulation voltage
- 2 kVeff / 5 s
- Insulation voltage input or output/rail
- 4 kVeff / 1 min.
- Insulation voltage input or output/supply
- 2 kVeff / 5 s
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Output
- Fine adjustment
- ± 12.5% of FSR
- load impedance current
- ≤ 600 Ω
- load impedance voltage
- ≥ 1 kΩ
- Number of outputs
- 1
- Offset current
- max. 100 µA
- Offset voltage
- max. 0.05 V
- Output current
- 0...20 mA, 4...20 mA
- Output voltage, note
- 0...10 V
- Status indicator
- Module active: LED on/ wire breakage: LED flashing/Error: LED off
- Wire break detection
- LED flashing (output value: > 20 mA, >10 V)
Probability Of Failure
- MTTF
- 267 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- 0 °C...55 °C
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- 0 °C
- Storage temperature
- -20 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
Tender Specification Sheets
- Long specification
- RTD measurement isolating transformer; configured with DIP switchesRTD measurement isolating transformer in 17.5 mm width with external power supply,for transmitting and isolating 2-/3-/-4-wire Cu10/ 25/ 50/ 100 signals. Analogue DC signals 0(4) to 20 mA / 0 to 10 V are available on the output side.Internal potentiometer is used for zero and span calibrations.Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 17.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input3-/4-wire Cu 10, Cu 25, Cu 50, Cu 100Output 0/4...20 mA 0...10 VLoad resistance < 600 Ohm/ Strom/> 1 kOhm/ voltageTransmission error < 0,8% v. E. (RTD) typ. 200 ppm / °CAuxiliary power 24 VDC +/- 25 %Power loss approx. 0.9 WAmbient temperature range 0°C...+55 °CIsolation EN 50178, 3-way isolation up to 4 kV AC/DC of all circuits against each otherTest voltage2 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULus, cULusEXType WAS5 PRO RTD Cu
- Short specification
- RTD measurement isolating transformer; configured with DIP switchesRTD measurement isolating transformer in 17.5 mm width with external power supply,for transmitting and isolating 2-/3-/-4-wire Cu10/ 25/ 50/ 100 signals. Analogue DC signals 0(4) to 20 mA / 0 to 10 V are available on the output side.Internal potentiometer is used for zero and span calibrations.