Description
Weidmuller 8581180000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CULUS, CULUSEX, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-28
- eClass 9.0
- 27-21-01-28
- eClass 9.1
- 27-21-01-28
- ETIM 6.0
- EC002918
- ETIM 7.0
- EC002918
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Stripping length, rated connection
- 7 mm
- Tightening torque, max.
- 0.5 Nm
- Tightening torque, min.
- 0.4 Nm
- Type of connection
- Screw connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 92.4 mm
- Length (inches)
- 3.638 inch
- Net weight
- 118.7 g
- Width
- 12.5 mm
- Width (inches)
- 0.492 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Accuracy
- < 0.2% of output range
- Configuration
- DIP switch (measurement range 0...15900 Hz), Frequency generator (measurement range 0...100 kHz)
- Current-carrying capacity of cross-connect.
- ≤ 2 A
- Galvanic isolation
- 3-way isolator
- Input/Output
- configurable
- Power consumption
- max. 1.6 W at IOUT = 20 mA
- Rail
- TS 35
- Step response time
- 360 ms + 2 times the period time of input frequency
- Temperature coefficient
- max. 200 ppm/K of output range
- Voltage supply
- 24 V DC ± 25 %
Input
- Input frequency
- 0…100kHz, adjustable
- Number of inputs
- 1
- Rated input level
- Threshold/hysteresis: Namur: approx. 1.7 mA/approx. 0.2 mA; NPN: approx. 6.5 V/approx. 0.2 V; PNP: approx. 6,7 V/approx. 0.5 V
- Sensor
- 2-, 3-wire PNP/NPN, Namur initiator, push-pull step, Frequency
- Sensor supply
- 16 V DC @ max. 15 mA
Insulation Coordination
- Clearance & creepage distances
- ≥ 5.5 mm
- EMC standards
- EN 55011, EN 61000-6, EN 61326
- Galvanic isolation
- 3-way isolator
- Impulse withstand voltage
- 6 kV
- Insulation voltage
- 4 kVeff / 5 s
- Insulation voltage input or output/rail
- 4 kVeff / 1 min.
- Insulation voltage input or output/supply
- 4 kVeff / 5 s
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Output
- load impedance current
- ≤ 600 Ω
- load impedance voltage
- ≥ 1 kΩ
- Number of outputs
- 1
- Offset current
- max. 100 µA
- Offset voltage
- max. 0.05 V
- Output current
- 0...20 mA, 4...20 mA, Adjustable
- Output voltage, note
- 0...5 V, 0...10 V, Adjustable
- Status indicator
- Green LED
Probability Of Failure
- MTTF
- 458 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- 0 °C...55 °C
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- 0 °C
- Storage temperature
- -20 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
Tender Specification Sheets
- Long specification
- Measurement isolating transformer for frequency signals, configured with DIP switchesf/DC measurement isolating transformer in 12.5 mm width, with external power supply:for transmitting, converting and isolating frequencies up to 100 kHz. Namur or 3-wire NPN/PNP sensors can be connected on the input side. Standard DC signals 0(4) to 20 mA/ 0 to 10 V are available on the output side.Internal potentiometer is used for zero and span calibrations.Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 12.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 2-, 3-wire PNP/ NPN, Namur initiators, push-pull up to 100 kHz Output 0/4...20 mA 0...10 V Load resistance < 600 Ohm/ Strom/> 1 kOhm/ voltageTransmission error <0.2 % of inputAuxiliary power 24 VDC +/- 25 %Power loss approx. 1.6 WAmbient temperature range 0°C...+55 °CIsolation EN 50178, 3-way isolation up to 4 kV AC/DC of all circuits against each otherTest voltage 2 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category III and pollution degree 2Approvals cULus, cULusEXType WAS4 PRO Freq
- Short specification
- Measurement isolating transformer for frequency signals, configured with DIP switchesf/DC measurement isolating transformer in 12.5 mm width, with external power supply:for transmitting, converting and isolating frequencies up to 100 kHz. Namur or 3-wire NPN/PNP sensors can be connected on the input side. Standard DC signals 0(4) to 20 mA/ 0 to 10 V are available on the output side. Internal potentiometer is used for zero and span calibrations.