Description
Weidmuller 8581170000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CULUS, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-20
- eClass 9.0
- 27-21-01-20
- eClass 9.1
- 27-21-01-20
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 1.5 mm²
- Stripping length, rated connection
- 7 mm
- Type of connection
- Tension-clamp connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 92.4 mm
- Length (inches)
- 3.638 inch
- Net weight
- 114 g
- Width
- 17.5 mm
- Width (inches)
- 0.689 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Accuracy
- typ. 0.1 %; max 0.2 %
- Configuration
- none
- Galvanic isolation
- Passive isolator
- Input/Output
- 4...20 mA/ 2 x 4...20 mA
- Rail
- TS 35
- Step response time
- < 20 ms
- Temperature coefficient
- ≤ 150 ppm/K
- Voltage supply
- min. 12 V DC/ max. 30 V DC
Input
- Input current
- 4...20 mA (current loop)
- Number of inputs
- 1
- Voltage drop
- 3.8 V
Insulation Coordination
- Clearance & creepage distances
- ≥ 5.5 mm
- EMC standards
- EN 55011, EN 61000-6
- Galvanic isolation
- Passive isolator
- Impulse withstand voltage
- 4 kV
- Insulation voltage
- 4 kVeff / 5 s
- Insulation voltage input or output/rail
- 4 kVeff / 1 min.
- Insulation voltage input or output/supply
- 4 kVeff / 5 s
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Output
- Cut-off frequency (-3 dB)
- 30 Hz
- load impedance current
- RL = (UB-12 V) / 20 ± 20mA, e.g. 600 Ω at 24 V
- Number of outputs
- 2
- Output current
- 2 x 4...20 mA (current loop)
- Output signal limit
- Approx. 31 mA
- Status indicator
- Green LED
Probability Of Failure
- MTTF
- 228 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- 0 °C...55 °C
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- 0 °C
- Storage temperature
- -20 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
Tender Specification Sheets
- Long specification
- Standard signal splitter, output-loop powered1-channel signal splitter in 17.5 mm width, output-loop powered, for transmitting and isolating analogue DC current signals from 0/4 to 20 mA. Add-on housing for TS35 DIN rail installation Dimensions: L/W/H 92.4/17.5/ 112.4 mm tension-clamp connection /nominal cross-section1.5 mm²Protection degree: IP 20 Input4...20 mAOutput 2 x 4...20 mA Load resistance/ R = (UB-12 V) / 20 mA e.g. 600 Ohm at 20 mA Transmission error Auxiliary power 4...20 mA output current loopAmbienttemperature range 0°C...+55 °C Isolation EN 50178 , 2-way isolation up to 4 kV AC/DC Test voltage4 kV Rated voltage 300 V AC/DC at overvoltage category III and pollution degree 2 Approvals cULus TypeWAZ5 CCC 2OLP
- Short specification
- Standard signal splitter, output-loop powered1-channel signal splitter in 17.5 mm width, output-loop powered, for transmitting and isolating analogue DC current signals from 4 to 20 mA.