Weidmuller 8540190000

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Weidmuller 8540190000 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- EAC
- CULUS
- CE
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 5.1
- 27-21-01-20
- eClass 6.2
- 27-21-01-20
- eClass 7.1
- 27-21-01-20
- eClass 8.1
- 27-21-01-20
- eClass 9.0
- 27-21-01-20
- eClass 9.1
- 27-21-01-20
- ETIM 3.0
- EC001774
- ETIM 4.0
- EC002653
- ETIM 5.0
- EC002653
- ETIM 6.0
- EC002653
- UNSPSC
- 31-12-10-07
Connection Data
- Clamping range, rated connection
- 1.5 mm²
- Clamping range, rated connection, max.
- 2.5 mm²
- Clamping range, rated connection, min.
- 0.5 mm²
- Stripping length, rated connection
- 7 mm
- Type of connection
- Tension clamp connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 92.4 mm
- Length (inches)
- 3.638 inch
- Net weight
- 127 g
- Width
- 17.5 mm
- Width (inches)
- 0.689 inch
General Data
- Accuracy
- 0.2 %
- Configuration
- none
- Current-carrying capacity of cross-connect.
- ≤ 2 A
- Galvanic isolation
- 3-way isolator
- Input/Output
- 0(4)...20 mA/0(4)...20 mA
- Mounting rail
- TS 35
- Power consumption
- < 1.5 W @ I
- = 20 mA
- Step response time
- ≤ 45 ms
- Supply voltage
- 24 V DC ± 25 %
- Temperature coefficient
- ± 250 ppm/K
General Ordering Data
- GTIN (EAN)
- 4032248180592
- Order No.
- 8540190000
- Qty.
- 1 pc(s).
- Type
- WAZ5 CCC 0-20/0-20mA
- Version
- Signal converter/insulator, Tension clamp connection
Input
- Input current
- 0...20 mA, 4…20mA
- Input resistance, current
- ≤ 110 Ω
- Number of inputs
- 1
Insulation Coordination
- Clearance & creepage distances
- ≥ 3 mm
- EMC standards
- EN 55011, EN 61000-6
- Galvanic isolation
- 3-way isolator
- Impulse withstand voltage
- 4 kV
- Insulation voltage
- 2 kV
- / 5 s
- Insulation voltage input or output/rail
- / 1 min.
- 4 kV
- Insulation voltage input or output/supply
- 2 kV
- / 5 s
- Pollution severity
- 2
- Rated voltage
- 300 V
- Standards
- DIN EN 50178, DIN EN 61000-4-2
- Surge voltage category
- III
Output
- Cut-off frequency (-3 dB)
- 10 Hz
- load impedance current
- ≤ 600 Ω
- Number of outputs
- 1
- Output current
- 0...20 mA, 4...20 mA
Probability Of Failure
- MTTF
- 373 Years
Product Information
- Descriptive text accessories
- Cross-connectors for power supplies and markers: refer to accessories
- Product information
- This product will soon be replaced by a new product.
- Please do not use with new systems. Please contact our technical support.
Temperatures
- Operating temperature
- 0 °C...55 °C
- Storage temperature
- -20 °C...85 °C