Weidmuller 8432300000

Estimated Delivery between and with free shipping.
Overnight shipping is also available.
Free Shipping
1 Year Warranty
A+ Rated On The BBB
Next Day Delivery
Based In The USA
Description
Weidmuller 8432300000 is now available new, surplus, and used from Williams Automation.
If you need a specific firmware or series relating to this item, please call or email us with your request.
We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you require one.
Please note we offer UPS Next Day Air shipping for all orders. Please be sure to select next day shipping at checkout, and we will provide same-day shipment.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- CE, CSA, CULUS, EAC
- ROHS
- Conform
- UL File Number Search
- E141197
Classifications
- eClass 10.0
- 27-21-01-29
- eClass 9.0
- 27-21-01-29
- eClass 9.1
- 27-21-01-29
- ETIM 6.0
- EC002919
- ETIM 7.0
- EC002919
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Stripping length, rated connection
- 7 mm
- Tightening torque, max.
- 0.5 Nm
- Tightening torque, min.
- 0.4 Nm
- Type of connection
- Screw connection
Dimensions And Weights
- Depth
- 112.4 mm
- Depth (inches)
- 4.425 inch
- Length
- 92.4 mm
- Length (inches)
- 3.638 inch
- Net weight
- 78.2 g
- Width
- 12.5 mm
- Width (inches)
- 0.492 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Configuration
- DIP switch
- Current-carrying capacity of cross-connect.
- ≤ 2 A
- Current consumption
- < 38 mA @ IOUT = 20 mA
- Galvanic isolation
- 2-way isolator
- Input/Output
- Thermocouple type: K, J, T, E, N, R, S, B / 0(4)...20 mA; 0...10 V
- Linearity
- Yes
- Rail
- TS 35
- Step response time
- without filter: 1.1 s; with filter: 6 s
- Temperature coefficient
- ± (200 ppm from the span + 0.075 K)/K
- Voltage supply
- 24 V DC ± 20 %
Input
- Number of inputs
- 1
- Sensor
- Thermo element (IEC 584) type: K,J,T,E,N,R,S,B
- Temperature input range
- -200...+1820 °C
Insulation Coordination
- EMC standards
- EN 55011, EN 61000-6
- Galvanic isolation
- 2-way isolator
Output
- cold junction compensation
- Yes
- load impedance current
- ≤ 500 Ω
- Number of outputs
- 1
- Offset current
- max. 100 µA
- Offset voltage
- max. 0.05 V
- Output current
- 0...20 mA, 4...20 mA
- Output voltage, note
- 0...10 V
- Status indicator
- Module active: LED on/ wire breakage: LED flashing/Error: LED off
- Wire break detection
- LED flashing (output value: > 20 mA, >10 V)
Probability Of Failure
- MTTF
- 317 Years
Product Information
- Product information
- This product will soon be replaced by a new product.Please do not use with new systems. Please contact our technical support.
Ratings Iecex/Atex/Cul
- Certificate no. (cULus)
- E141197
Temperatures
- Operating temperature
- 0 °C...55 °C
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- 0 °C
- Storage temperature
- -20 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
Tender Specification Sheets
- Long specification
- TC temperature measuring transformer; configured with DIP switchesTC- temperature measuring transformer in 12.5 mm width with external power supply,for transmitting thermocouples (insulated version) types K, J, T, E, N, R, S and B according to IEC 584. Standard DC signals 0(4) to 20 mA/ 0 to 10 V are available on the output side.Internal cold-junction compensationInternal potentiometer is used for zero and span calibrations.Add-on housing for TS35 rail mountingDimensions: L/W/H 92.4/ 12.5/ 112.4 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input TC Type Type K, J, T, E, N, R, S Output 0/4...20 mA 0...10 V Load resistance < 500 Ohm/ Strom/> 1 kOhm/ voltageTransmission error 0.2...0.3 0.8 % of input (depending on TC Type) Temperature coefficient +/- (200 ppm of end value + 0.075 K)/KAuxiliary power 24 VDC +/- 20 °Power loss approx. 0.7 WAmbient temperature range 0°C...+55 °C Ratedvoltage 300 VAC/DC at overvoltage category III and pollution degree 2Approvals cULus, CSAType WTS4 THERMO
- Short specification
- TC temperature measuring transformer; configured with DIP switchesTC- temperature measuring transformer in 12.5 mm width with external power supply,for transmitting thermocouples (insulated version) types K, J, T, E, N, R, S and B according to IEC 584. Standard DC signals 0(4) to 20 mA/ 0 to 10 V are available on the output side.Internal cold-junction compensationInternal potentiometer is used for zero and span calibrations.
Reviews
What our customers say
Rating