Approvals
- Approvals
- EAC
Classifications
- eClass 10.0
- 27-21-01-20
- eClass 9.0
- 27-21-01-20
- eClass 9.1
- 27-21-01-20
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Tightening torque, max.
- 0.6 Nm
- Tightening torque, min.
- 0.4 Nm
- Type of connection
- Screw connection
- Wire connection cross section AWG, max.
- AWG 12
- Wire connection cross section AWG, min.
- AWG 26
Dimensions And Weights
- Depth
- 114 mm
- Depth (inches)
- 4.488 inch
- Height
- 117.2 mm
- Height (inches)
- 4.614 inch
- Net weight
- 100 g
- Weight
- 126 g
- Width
- 12.5 mm
- Width (inches)
- 0.492 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Accuracy
- < 0.2 % of end value
- Configuration
- none
- Galvanic isolation
- 2-way isolator
- Rail
- TS 35
- Step response time
- ≤ 1 ms
- Temperature coefficient
- ≤ 100 ppm/K
- Voltage supply
- via output current loop, min. 12 V DC/ max. 30 V DC
Input
- Input resistance, voltage
- ≥ 300 kΩ
- Input voltage
- 0...10 V
- Number of inputs
- 1
- Sensor
- Voltage source
Insulation Coordination
- EMC standards
- EN 61010-1:2011, UL 61010-1, IEC61000-6-2, IEC 61000-6-4
- Galvanic isolation
- 2-way isolator
- Impulse withstand voltage
- 4 kV (1.2/50 µs)
- Insulation voltage
- 2 kV (Input /Output), 1 min, 50 Hz
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Output
- load impedance current
- ≤ 600 Ω
- Number of outputs
- 1
- Output current
- 4...20 mA, loop-powered
Product Information
- Product information
- The ACT20P-VIX-CO-OLP-S single-channel fixed passive isolator isolates and converts analogue standard signals. An analogue input voltage signal is linearly converted into an analogue output current signal and galvanically isolated. The device is powered via the output current loop. Features 2-way galvanic isolation between input and output.
Temperatures
- Ambient temperature
- -20 °C...+60 °C
- Humidity
- 5...95 %, no condensation
- Operating temperature
- -20 °C...60 °C
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Storage temperature
- -40 °C...85 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -40 °C