Complementary
- Air Flow
- internal circuit 1450 m3/h 60 Hz || external circuit 1450 m3/h 60 Hz
- Ambient Air Temperature For Operation
- outside the enclosure 20-45 °C || maximum 45-45 °C || inside the enclosure 20-45 °C
- Color
- Gray RAL 7035)
- Control Type
- electronic controller
- Cooling Gas Type
- R134a 0.84 kg)
- Depth
- 336 mm
- Energy Efficiency Ratio
- 2.4
- Height
- 1270 mm
- Inrush Current
- 14 A
- Line Rated Current
- 2.6 A
- Material
- stainless steel
- Net Weight
- 84 kg
- Noise Level
- 70 dB
- Power Consumption In W
- 1220 W 60 Hz, L35-L35 || 1440 W 60 Hz, L35-L50
- Pressure
- 25 bar
- Protection Type
- thermal protection T 6 A || short-circuit protection (magnetic)
- Temperature Setting Range
- 20-45 °C
- Type Of Ventilation Filter
- optional external circuit filter
- Width
- 500 mm
Environment
- Ip Degree Of Protection
- IP54 IEC 60529 on the internal circuit) || IP34 IEC 60529 on the external circuit)
- Product Certifications
- UL
- Standards
- DIN 3168
Offer Sustainability
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Eu Rohs Directive
- Compliant
- Mercury Free
- Yes
- Reach Free Of Svhc
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- Rohs Exemption Information
- Yes
- Toxic Heavy Metal Free
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Specifications
- Cooling Power
- 9900 Btu/h 60 Hz L35-L35 || 7680 Btu/h 60 Hz L35-L50
- Kw Rating
- 3300 W
- Mounting Location
- side
- Mounting Mode
- by screws
- Product Destination
- for enclosure
- Product Name
- CU
- Product Or Component Type
- cooling unit
- Range
- ClimaSys