Schneider Electric NSYCUHD1K6

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Schneider Electric NSYCUHD1K6 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Complementary
- Air Flow
- internal circuit 570 m3/h 50/60 Hz || external circuit 1050 m3/h 50/60 Hz
- Ambient Air Temperature For Operation
- inside the enclosure 20-46 °C || maximum 55-55 °C || outside the enclosure -20-55 °C 50/60 Hz
- Color
- Gray RAL 7035)
- Control Type
- mechanical
- Cooling Gas Type
- R134a 0.45 kg)
- Depth
- 237 mm
- Energy Efficiency Ratio
- 1.9
- Height
- 999 mm
- Inrush Current
- 18 A
- Line Rated Current
- 5.4 A
- Material
- steel
- Net Weight
- 40 kg
- Noise Level
- 65 dB EN/ISO 3746
- Power Consumption In W
- 850 W 50/60 Hz, L35-L35 || 970 W 50/60 Hz, L35-L50
- Pressure
- 25 bar
- Protection Type
- thermal protection T 10 A || short-circuit protection (magnetic)
- Temperature Setting Range
- 20-55 °C
- Type Of Ventilation Filter
- optional external circuit filter
- Width
- 405 mm
Environment
- Directives
- 2006/42/EC - machinery || 2004/108/EC - electromagnetic compatibility || 2006/95/EC - low voltage directive
- Ip Degree Of Protection
- IP55 IEC 60529 on the internal circuit) || IP34 IEC 60529 on the external circuit)
- Product Certifications
- CE
- Standards
- EN 60204-1 || EN 378 || EN/ISO 12100 || EN 60335-1 || EN 60335-2-40
Offer Sustainability
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- ENVEOLI2106024EN
- Environmental Disclosure
- ENVPEP2106024EN
- Eu Rohs Directive
- Compliant
- Mercury Free
- Yes
- Reach Free Of Svhc
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- Rohs Exemption Information
- Yes
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Specifications
- Cooling Power
- 1600 W 50/60 Hz L35-L35 || 1230 W 50/60 Hz L35-L50
- Kw Rating
- 1600 W
- Mounting Location
- side
- Mounting Mode
- by screws
- Product Destination
- for enclosure
- Product Name
- CU
- Product Or Component Type
- cooling unit
- Range
- ClimaSys
Reviews
What our customers say