Phoenix Contact 2920308

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Phoenix Contact 2920308 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Ambient conditions
- Altitude
- ≤ 2000 m (amsl (above mean sea level))
- Ambient temperature (operation)
- -40 °C - 80 °C
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Degree of protection
- IP20
- Permissible humidity (operation)
- 5 % - 95 %
- Shock (operation)
- 30g
- Vibration (operation)
- 7.5g
Dimensions
- Depth
- 67.3 mm
- Height
- 47 mm
- Horizontal pitch
- 1 Div.
- Width
- 17.7 mm
Protective circuit
- Impulse discharge current (10/350) µs, charge
- 1.25 As
- Impulse discharge current (10/350) µs, peak value limp
- 2.5 kA
- Impulse discharge current (10/350) µs, specific energy
- 1.56 kJ/Ω
- Max. backup fuse with branch wiring
- 250 A AC (gG)
- Maximum continuous voltage UC
- 385 V AC
- Maximum discharge current Imax (8/20) µs
- 65 kA
- Nominal discharge current In (8/20) µs
- 30 kA
- Nominal frequency fN
- 50 Hz (60 Hz)
- Nominal voltage UN
- 240/415 V AC (TT)
- 240/415 V AC (TN)
- Residual current IPE
- ≤ 600 µA
- Residual voltage Ures
- ≤ 1.2 kV (at 5 kA)
- ≤ 1.8 kV (at In)
- ≤ 1.3 kV (at 10 kA)
- ≤ 1.15 kV (at 3 kA)
- Response time tA
- ≤ 25 ns
- Short-circuit current rating ISCCR
- 25 kA
- Standby power consumption PC
- ≤ 230 mVA
- TOV behavior at UT
- 480 V AC (5 s / withstand mode)
- Voltage protection level Up
- ≤ 1.8 kV
Standards and Regulations
- Standards/regulations
- IEC 61643-11 2011
- EN 61643-11 2012
Reviews
What our customers say
Rating