Ambient conditions
- Ambient temperature (operation)
- -20 °C - 65 °C
- Ambient temperature (storage/transport)
- -25 °C - 80 °C
- Degree of protection
- IP20
- Noise immunity
- EN 61000-6-2
- Permissible humidity (operation)
- 15 % - 85 %
Coil side
- Function
- F: Flashing beginning with pulse
- Input voltage range
- 24 V DC (19.2 V DC ...30 V DC)
- Setting range time
- 0.3 min. - 30 min.
Connection data
- Conductor cross section AWG
- 26 - 14
- Conductor cross section flexible
- 0.14 mm² - 2.5 mm²
- Conductor cross section solid
- 0.14 mm² - 2.5 mm²
- Connection method
- Push-in connection
- Stripping length
- 8 mm
Contact side
- Contact type
- 1 floating PDT
- Interrupting rating (ohmic load) max.
- 1125 VA (4.5 A/250 V AC, module mounted in rows, spacing ≤ 5 mm)
- Output fuse
- 6.3 A (fast-blow)
Control contact
- Control pulse length
- min. 50 ms
Dimensions
- Depth
- 86 mm
- Height
- 80 mm
- Width
- 6.2 mm
Environmental Product Compliance
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
- Environmentally Friendly Use Period = 50 years
- REACh SVHC
- Lead 7439-92-1
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC Directive 2004/108/EC
- Insulation
- Safe isolation
- Low Voltage Directive
- Conformance with LV directive 2006/95/EC
- Noise emission
- EN 61000-6-4
- Noise immunity
- EN 61000-6-2
- Overvoltage category
- III
- Pollution degree
- 2
- Rated insulation voltage
- 300 V AC
- Rated surge voltage
- 6 kV
- Standards/regulations
- EN 50178