OMRON LY2N DC24

Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
OMRON LY2N DC24 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Ratings / Performance
- Ambient humidity (Operating)
- 5 to 85%RH (with no icing or condensation)
- Ambient temperature (Operating)
- -25 to 40 °C (with no icing or condensation)
- Coil ratings
- 24 VDC 36.9 mA
- Coil resistance
- 650 Ω
- Coil surge killer
- Not equipped
- Contact material
- Contact finish: Nothing
- Contact body: Ag alloy
- Contact method
- Single
- Contact rated load
- 110 V AC7.5 A (Inductive load (cos phi = 0.4))
- 24 VDC 10 A (Resistive load)
- 24 VDC 5 A (Inductive load (L/R = 7 ms))
- 110 V AC10 A (Resistive load (cos phi = 1))
- Contact resistance
- Max. 50 mOhm, Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A
- Contact type
- DPDT
- Dielectric strength
- Between contacts of same polarity: 1000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Between coil and contacts: 2000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Between contacts of different polarity: 2000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Endurance (Electrical)
- 500000 operations Min.
- Endurance (Mechanical)
- 100000000 operations Min.
- Failure rate
- 100 mA at 5 VDC (failure level: P Reference value)
- Insulation resistance
- Between coil and contacts: 100 MΩ min. (at 500 VDC)
- Between contacts of different polarity: 100 MΩ min. (at 500 VDC)
- Between contacts of same polarity: 100 MΩ min. (at 500 VDC)
- Maximum switching current
- AC: 10 A
- DC: 10 A
- Maximum switching power
- DC: 120 W (Inductive load (L/R = 7 ms))
- DC: 240 W (Resistive load)
- AC: 1100 VA (Resistive load (cos phi = 1))
- AC: 825 VA (Inductive load (cos phi = 0.4))
- Maximum switching voltage
- 250 VAC (Resistive load (cos phi = 1))
- 125 VDC (Resistive load)
- Max. voltage
- 110 % (of rated voltage)
- Operate voltage (Set voltage)
- 80 % max.
- Operating indicator
- LED indicator
- Operating time (set time)
- 25 ms
- Power consumption
- 0.9 W max.
- Product classification
- Monostable relays
- Built-in LED indicator type
- Protective structure
- Closed type (cover)
- Release time (Reset time)
- 25 ms
- Release voltage (Reset voltage)
- 10 % Min.
- Shock resistance (Destruction)
- 1000 m/s**2, 3 times each in directions
- Shock resistance (Malfunction)
- 200 m/s**2
- Terminal structure
- Plug-in
- Vibration resistance (Destruction)
- 10 to 55 to 10 Hz, 0.5-mm single amplitude 2 hours each in X, Y, and Z directions
- Vibration resistance (Malfunction)
- 10 to 55 to 10 Hz, 0.5-mm single amplitude in each direction
- Weight
- Approx.40 g
Reviews