OMRON LY2 AC110/120
Description
OMRON LY2 AC110/120 is now available new, surplus, and used from Williams Automation.
If you need a specific firmware or series relating to this item, please call or email us with your request.
We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you require one.
Please note we offer UPS Next Day Air shipping for all orders. Please be sure to select next day shipping at checkout, and we will provide same-day shipment.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Ratings / Performance
- Ambient_humidity (Operating)
- 5 to 85%RH (with no icing or condensation)
- Ambient temperature (Operating)
- -25 to 55 °C (with no icing or condensation)
- Coil ratings
- 110 VAC 9.9 mA (50 Hz) / 110 VAC 8.4 mA (60 Hz) / 120 VAC 10.8 mA (50 Hz) / 120 VAC 9.2 mA (60 Hz)
- Coil resistance
- 4430 Ω
- Coil surge killer
- Not equipped
- Contact material
- Contact body: Ag alloy
- Contact finish: Nothing
- Contact method
- Single
- Contact rated load
- 24 VDC 5 A (Inductive load (L/R = 7 ms))
- 110 V AC7.5 A (Inductive load (cos phi = 0.4))
- 110 V AC10 A (Resistive load (cos phi = 1))
- 24 VDC 10 A (Resistive load)
- Contact resistance
- Max. 50 mOhm, Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A
- Contact type
- DPDT
- Dielectric strength
- Between contacts of same polarity: 1000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Between contacts of different polarity: 2000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Between coil and contacts: 2000 V (Leakage current 3 mA 50/60 Hz 1 min)
- Endurance (Electrical)
- 500000 operations Min.
- Endurance (Mechanical)
- 50000000 operations Min.
- Failure rate
- 100 mA at 5 VDC (failure level: P Reference value)
- Insulation resistance
- Between contacts of same polarity: JA:100 MΩ min. (at 500 VDC)
- Between coil and contacts: JA:100 MΩ min. (at 500 VDC)
- Between contacts of different polarity: JA:100 MΩ min. (at 500 VDC)
- Maximum switching current
- DC: 10 A
- AC: 10 A
- Maximum switching power
- DC: 120 W (Inductive load (L/R = 7 ms))
- DC: 240 W (Resistive load)
- AC: 825 VA (Inductive load (cos phi = 0.4))
- AC: 1100 VA (Resistive load (cos phi = 1))
- Maximum switching voltage
- 125 VDC (Resistive load)
- 250 VAC (Resistive load (cos phi = 1))
- Max. voltage
- 110 % (of rated voltage)
- Operate voltage (Set voltage)
- 80 % max.
- Operating indicator
- Not equipped
- Operating time (set time)
- 25 ms
- Power consumption
- 0.9 to 1.1 VA (60 Hz)
- Product classification
- Monostable relays
- Standard type
- Protective structure
- Closed type (cover)
- Release time (Reset time)
- 25 ms
- Release voltage (Reset voltage)
- 30 % Min.
- Shock resistance (Destruction)
- 1000 m/s**2, 3 times each in directions
- Shock resistance (Malfunction)
- 200 m/s**2
- Terminal structure
- Plug-in
- Vibration resistance (Destruction)
- 10 to 55 to 10 Hz, 0.5-mm single amplitude 2 hours each in X, Y, and Z directions
- Vibration resistance (Malfunction)
- 10 to 55 to 10 Hz, 0.5-mm single amplitude in each direction
- Weight
- Approx.40 g