OMRON H3CA-A
Description
OMRON H3CA-A is now available new, surplus, and used from Williams Automation.
If you need a specific firmware or series relating to this item, please call or email us with your request.
We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you require one.
Please note we offer UPS Next Day Air shipping for all orders. Please be sure to select next day shipping at checkout, and we will provide same-day shipment.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Ratings / Performance
- Accessory (sold separately)
- Y92F-30: Flush Mounting Adapter
- Y92F-70: Flush Mounting Adapter
- Y92F-71: Flush Mounting Adapter
- Y92A-48D: Soft Cover
- Y92A-48B: Hard Cover
- Accuracy of operating time
- +/- 0.3% +/- 0.05 s (The values are based on the set value.)
- Ambient humidity
- Operating: 35 to 85%RH
- Storag: 35 to 85%RH
- Ambient temperature
- Operating: -10 to 55 °C
- Storag: -25 to 65 °C (with no icing or condensation)
- Case color
- Light gray (Munsell 5Y7/1)
- Control output (Contact output)
- Type: Time-limit contact: SPDT
- Minimum applicable load: 10 mA at 5 VDC (failure level: P)
- Switching capacities (Inductive load): 1 A 250 VAC (cos phi=0.4) / 2.5 A 24 VDC ( L/R=7 ms)
- Switching capacities (Resistive load): 3 A at 250 VAC
- Degree of protection
- Panel surface: IP40
- Dielectric strength
- between control output terminals and operating circuit: 2000
- between non-continuous contacts: 1000
- between current-carrying metal parts and non-curernt-carrying metal parts: 2000
- Display method
- LCD
- Electrical life
- 100000 operations min. (3 A at 250 VAC resistive load at 1800 operations/h)
- External connection method
- 11-pin round socket
- Impulse withstand voltage
- 5 kV
- Influence of temperature
- +/- 0.3% +/- 0.05 s (The values are based on the set value.)
- Influence of voltage
- +/- 0.3% +/- 0.05 s (The values are based on the set value.)
- Input method
- No-voltage input
- Input signals
- Start, Reset, Gate, Check
- Insulation resistance
- 100 MΩ min. (at 500 VDC)
- between current-carrying terminals and exposed non-curernt-carrying metal parts / between control output terminals and operating circuit / between non-continuous contacts
- Mechanical life
- 10000000 operations min. (under no load at 1800 operations/h)
- Minimum input signal width
- 0.05 s(Reset, Gate)
- Mounting method
- Flush mounting / Surface mounting
- Noise immunity
- Between input terminals: +/- 600 V(0 to 360 degrees)
- Square-wave noise by noise simulator (Pulse width: 100 ns/1 us, Rise: 1-ns)
- Between power terminals: +/- 2 kV(0 to 360 degrees)
- Operating voltage range
- 90% to 110% of rated supply voltage (21.6 to 264 VAC/10.8 to 264 VDC)
- Output modes
- B (Repeat cycle)
- F (One shot flicker)
- D (Signal OFF delay)
- C (Signal ON/OFF delay)
- E (Interval)
- H (Signal OFF delay)
- G (Signal ON/OFF delay)
- A (ON delay)
- Power consumption
- Approx. 0.2 to 2W
- Approx. 0.2 to 4VA
- Power reset
- Reset time: 0.5 s max.
- Rated supply voltage
- 24 to 240 VAC 50/60 Hz
- 12 to 240 VDC
- Reset system
- Self-reset/External reset
- Select method
- Thumbwheel Switch
- Setting error
- +/- 0.5% +/- 0.05 s (The values are based on the set value.)
- Shock resistance (Destruction)
- 1000 m/s**2, in each 6 directions (3 axes) 3 times
- Shock resistance (Malfunction)
- 100 m/s**2, in each 6 directions (3 axes) 3 times
- Time ranges
- 0.1 s to 99.9 s / 1 s to 999 s / 0.1 min to 99.9 min / 1 min to 999 min / 0.1 h to 99.9 h / 1 h to 999 h / 10 h to 9990 h
- Time ranges(Number of ranges)
- 7
- Vibration resistance (Destruction)
- 10 to 55 Hz, 0.75 mm single amplitude in each 3 directions for 1 hour
- Vibration resistance (Malfunction)
- 10 to 55 Hz 0.5 mm single amplitude in each 3 directions for 10 min
- Weight
- Approx. 110g