Description
Mersen MPDB67493 is now available new, surplus, and used from Williams Automation.
If you need a specific firmware or series relating to this item, please call or email us with your request.
We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you require one.
Please note we offer UPS Next Day Air shipping for all orders. Please be sure to select next day shipping at checkout, and we will provide same-day shipment.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Specifications
- Adder Poles
- All sizes have optional adder poles for increased flexibility and ease-of-use. Adder poles can be stacked to form multi-pole units in the field without the use of tools. Adder poles allow for customization of primary and secondary wire combinations. End barriers are also available for sale, catalog numbers can be found in the catalog number selection tables for each size block.
- Ampere Rating Al
- 310 A
- Ampere Rating Cu
- 380 A
- Body Insulating Material
- GFPC
- Connector Material
- Tin-plated Aluminum
- Connector Type Primary
- Box
- Connector Type Secondary
- Box
- Country Of Origin
- MX
- Flammability Rating
- 94 V-0
- Hex Screw Size And Type Primary
- 13/16-16 x 1.06
- Hex Screw Size And Type Secondary
- 8-32 (.164) x .25
- Hole Diameter Primary
- 0.88 in
- Hole Diameter Secondary
- 0.14 in
- Installation Mounting
- Direct Screw Mount
- Insulators
- Insulators are virtually unbreakable, made of glass-filled polycarbonate. “See-through,” hinged safety covers are optional and provide a greater degree of safety and shock resistance where required. Hinged covers can be installed without tools.
- Max Operating Temp
- 80 °C
- Max Storage Temp
- 80 °C
- Min Storage Temp
- -25 °C
- Number Of Openings Per Pole Primary
- 1
- Number Of Openings Per Pole Secondary
- 18
- Number Of Poles
- 3-pole
- Product Line
- MPDB Series UL 1953 Open-Style Power Distribution Blocks
- Rated Voltage Ac Ul
- 1000 V
- Rated Voltage Dc Ul
- 1000 V
- Safety Covers
- Polycarbonate safety covers provide dead-front protection. One cover is needed for each pole. Each cover has a test probe hole in the center for circuit checking. Covers are optional accessories and catalog numbers can be found in the catalog selection tables for each size block.
- Short Circuit Rating Class Cc
- 30 kA
- Short Circuit Rating Class G
- 60 kA
- Short Circuit Rating Class J
- 400 kA
- Short Circuit Rating Class L
- 400 kA
- Short Circuit Rating Class Rk1
- 200 kA
- Short Circuit Rating Class Rk5
- 100 kA
- Short Circuit Rating Class T
- 400 kA
- Short Circuit Rating Standalone
- 10 kA
- Spacings
- 1 inch through air and 2 inches over surface between uninsulated live parts of opposite polarity meets requirements for feeder and branch circuit applications of UL508A.
- Torque Rating Primary
- 500-#4 500
- Torque Rating Secondary
- #10-#14 15
- Wire Connectors
- Standard aluminum and copper wire connectors are available. Aluminum connectors accept both AL or CU wire while copper connectors accept CU wire only. Connectors are all 1-piece tin-plated. Many part numbers are rated to accept DLO-type fine-strand wire, allowing users to connect flexible conductors.
- Wire Insulation Rating
- 60/75C
- Wire Range Primary
- 500-#4
- Wire Range Secondary
- #10-#14
- Wire Type
- Solid/Stranded CU