Specifications
- Analog Inputs
- 6 Universal Inputs
- Analog Outputs
- 3 Analog Outputs
- Application
- Conventional and Heat Pump
- Digital Inputs
- 4 Digital Inputs ; 6 Universal Inputs
- Digital Output
- 8 Relay Outputs
- For Use With
- LCBS Connect ; LCBS Connect Gateway (LGW1000)
- Includes
- CRL6438SR Configurable CVAHU Controller ; TS120 Temperature and Humidity Wall Module
- Maximum Operating Ambient Temperature
- 150 °F (Controller); 122 °F (Wall Module) |65.5 °C (Controller); 50 °C (Wall Module)
- Maximum Operating Humidity
- 95 % non-condensing
- Minimum Operating Ambient Temperature
- -40 °C (Controller); 0 °C (Wall Module) |-40 °F (Controller); 32 °F (Wall Module)
- Minimum Operating Humidity
- 5 % non-condensing
- Mounting
- Sensor is mounted horizontally
- Network Communications
- LonWorks ; Sylk Bus
- Overall Depth
- 2.26 in (Controller); 0.83 in (Wall Module) |57 mm (Controller); 21 mm (Wall Module)
- Overall Height
- 138 mm (Controller); 84 mm (Wall Module) |5.45 in (Controller); 3.31 in (Wall Module)
- Overall Width
- 174 mm (Controller); 121 mm (Wall Module) |6.85 in (Controller); 4.77 in (Wall Module)
- Setpoint
- 32 to 122 °F ; 0 to 50 °C
- Supply Voltage
- 24 V AC
- Supply Voltage Frequency
- 50 Hz ; 60 Hz
- Thermostat Accuracy
- Sensor accuracy: ±0.36 F at 77 F, ±3% RH