Harting 20310200102

Estimated Delivery between and with free shipping.
Overnight shipping is also available.
Free Shipping
1 Year Warranty
A+ Rated On The BBB
10% Off First Order
Based In The USA
Description
Harting 20310200102 is now available from Williams Automation.
If you need a specific firmware version or series for this item, please call or email us with your request. We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you need one.
We offer Overnight shipping for most items listed on our website. Please get in touch with us to confirm whether the product can ship overnight on the day of your order. Cutoff times are typically 2-3 PM EST. Lead times can range from 1 to 4 business days.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Commercial data
- Country of origin
- Germany
- eCl@ss
- 27210902 Current transformer
- European customs tariff number
- 90303370
- Net weight
- 144.86 g
- Packaging size
- 1
Identification
- Element
- Current sensor
- Features
- Hall effect compensated current sensor || Measurable currents: AC, DC, pulsed, mixed ... || High accuracy over the entire measuring range || Galvanic insulation between primary and secondary current || Switchboard mounting || Housing material and potting mass have a flammability rating UL 94 V-0 || Applications: frequency converters, electrical drives, switched mode power suppplies, UPS
- Sensor technology
- Hall-Effekt || Closed loop
- Series
- HCM
Material properties
- China RoHS
- e
- ELV status
- compliant
- Material flammability class acc. to UL 94
- V-0
- Material (hood/housing)
- Polycarbonate (PC)
- REACH ANNEX XIV substances
- No
- REACH Annex XVII substances
- No
- REACH SVHC substances
- No
- RoHS
- compliant
Specifications and approvals
- Approvals
- DNV GL
- CE
- Yes
- Specifications
- EN 50178 || IEC 61373
Technical characteristics
- di/dt with optimal coupling
- > 100 A/µs
- f Frequency
- 0 ... 100 kHz
- I C Current consumption @ U C min
- 19 mA + I
- I O Offset current @ I P = 0 A, T A = 25 °C
- ± 0.3 mA
- I OT maximum temperature drift of I O
- ± 0.8 mA
- I PM Primary current, measuring range
- [0] ... [±300 A]
- I PN Nominal primary current
- 200 A
- I SN Nominal secondary current
- 100 mA
- K N Turns ratio
- 1 : 2000
- K s Creepage distance
- 49 mm
- L s Clearance distance
- 43.3 mm
- Overvoltage category
- III
- Pollution degree
- 2
- R M Measuring resistance @ I PM max , U C max , T A max
- 5 ... 58 Ω For other primary currents see diagram.
- R S Secondary coil resistance @ T A max
- 25 Ω
- T A Ambient temperature
- -40 ... +85 °C
- Tightening torque
- 4 Nm (2x steel screw M5)
- t r Response time @ I PN
- < 1 µs
- T S Storage temperature
- -45 ... +90 °C
- U B Rated voltage
- 600 V
- U C Power supply
- ±12 ... ±15 V ±5 %
- U D Test voltage, effective (50 Hz, 1 min)
- 3 kV Primary - secondary
- U St Rated impulse voltage (1,2/50 µs)
- 10 kV
- X Overall accuracy @ I PN , T A = 25 °C
- ± 0.8 %
- Ε L Linearity
- < 0.1 %
Version
- Field of application
- Industrial version
- Pack contents
- Counter connector included
- Termination
- Spring clamp termination
Reviews
What our customers say
Rating