Weidmuller 7760054123

Estimated Delivery between and with free shipping.
Overnight shipping is also available.
Free Shipping
1 Year Warranty
A+ Rated On The BBB
Next Day Delivery
Based In The USA
Description
Weidmuller 7760054123 is now available new, surplus, and used from Williams Automation.
If you need a specific firmware or series relating to this item, please call or email us with your request.
We can also provide specifications and/or a data sheet for this item upon request. Please call or email us if you require one.
Please note we offer UPS Next Day Air shipping for all orders. Please be sure to select next day shipping at checkout, and we will provide same-day shipment.
Call (803) 761-7027 if you have any questions about availability, or email us at sales@williamsautomation.com.
Approvals
- Approvals
- EAC
Classifications
- eClass 10.0
- 27-21-01-23
- eClass 9.0
- 27-21-01-23
- eClass 9.1
- 27-21-01-23
- ETIM 6.0
- EC002475
- ETIM 7.0
- EC002475
Connection Data
- Clamping range, max.
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, rated connection
- 2.5 mm²
- Tightening torque, max.
- 0.6 Nm
- Tightening torque, min.
- 0.4 Nm
- Type of connection
- Screw connection
- Wire connection cross section AWG, max.
- AWG 12
- Wire connection cross section AWG, min.
- AWG 26
Dimensions And Weights
- Depth
- 114 mm
- Depth (inches)
- 4.488 inch
- Height
- 117.2 mm
- Height (inches)
- 4.614 inch
- Net weight
- 100 g
- Weight
- 126 g
- Width
- 12.5 mm
- Width (inches)
- 0.492 inch
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
General Data
- Accuracy
- < 0.1 % of end value
- Configuration
- none
- Galvanic isolation
- 2-way isolator
- Rail
- TS 35
- Step response time
- ≤ 1 ms
- Temperature coefficient
- ≤ 100 ppm/K
- Voltage supply
- Loop powered, via 4…20 mA input
Input
- Input current
- 0(4)...20 mA current loop
- Number of inputs
- 1
- Sensor
- Current source
- Voltage drop, current input
- 3.8 V
Insulation Coordination
- EMC standards
- EN 61010-1:2011, UL 61010-1, IEC61000-6-2, IEC 61000-6-4
- Galvanic isolation
- 2-way isolator
- Impulse withstand voltage
- 4 kV (1.2/50 µs)
- Insulation voltage
- 2 kV inputs / outputs
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Output
- load impedance current
- ≤ 600 Ω
- Number of outputs
- 1
- Output current
- 0(4)...20 mA
Product Information
- Product information
- The ACT20P-CI-CO-ILP-S fixed passive isolators isolate analogue standard current source signals. An analogue input current signal is converted linear and galvanic isolated into an analogue output current signal. The device is powered via the input current loop. Features Galvanic 2-way isolation (single-channel device) between input and output.
Temperatures
- Ambient temperature
- -20 °C...+60 °C
- Humidity
- 5...95 %, no condensation
Reviews
What our customers say
Rating