Hardware
- Current Load
- 24 VDC nominal @ 300 mA
- 10 to 36 VDC @ 610 mA maximum
- Dimensions (H x W x D)
- 5.38 x 1.99 x 4.38 in 13.67 x 5.05 x 11.13 cm
- Operating Temperature
- -25°C to 70°C (-13°F to 158°F )
- Power Supply
- Positive, Negative, GND Terminals
- 10 to 36 VDC allowed
- 24 VDC nominal
- Relative Humidity
- 5% to 95% RH with no condensation
- Shipped With Each Unit
- ProSoft Solutions DVD
- J180 Power Connector
- 2.5 mm screwdriver
- 5’ straight-through Ethernet cable
- Shock
- IEC 60068-2-27; 30G @ 18ms, 3-Axis (Non-Operational)
- IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational)
- Storage Temperature
- -40°C to 80°C (-40°F to 176°F )
- Vibration
- IEC 60068-2-6; 5G @ 10 to 150 Hz
Modbus TCP/IP Specifications
- Command List
- Up to 160 fully configurable client commands
- Up to 100 commands per client, each fully configurable for Function Code, slave address, register to/from addressing and word/bit count.
- Command List Polling
- Each command can be individually enabled or disabled; write-only-on-data-change is available
- Status Data
- Error codes reported individually for each command
- Supported clients
- 10
- Supported Modbus Function Codes
- Read Holding Registers
- Force (Write) Single Coil
- Preset (Write) Multiple Holding Registers
- Read Input Status
- Mask Write Holding Register (server only)
- Read Coil Status
- Force (Write) Multiple Coils
- Read/Write Holding Registers (server only)
- Read Input Registers
- Preset (Write) Single Holding Register
- Supported servers
- MBAP = 5, Encapsulated = 5
PROFINET Specifications
- Driver Type
- Class A Device
- Exchange Types
- Cyclic Real-time (RT) and Acyclic Data
- PROFINET I/O Data
- 1440 bytes IN, 1440 bytes OUT
Williams Automation sells ProSoft parts at huge savings. Search to find the part you need today. If you can't find what you are looking for please Request A Quote from us and we will provide a timely response. You can also call us at 803-761-7027. We look forward to working with you to assist in the best way we can for your industrial needs.